.jpg)
| Item | Value |
|---|---|
| Measured gases | CO2carbon dioxide |
| Measuring range | 0-5000ppm (standard) |
| Detection principle | infrared |
| Accuracy | ±30ppm +3%F.S |
| Resolution | 1ppm |
| Response time | T90 < 60 seconds |
| Ingress protection | |
| Explosion protection | |
| Operating temperature | 0~50℃ |
| Power supply | |
| Output signal |
HT-86 carbon dioxide detection controller
HT-86 carbon dioxide detection controller adopts infrared gas detection and sensing unit, with high measurement accuracy, fast response speed and long service life. It can monitor the concentration of CO2 gas in the air environment in real time and display the value through the LCD screen. The fresh air system can be automatically controlled to turn on and off according to the change of CO2 concentration in the environment, and the alarm value (turn on the control device) and the alarm release value (turn off the control device) can be set freely.
The instrument comes standard with a passive contact relay switch signal, which can be optionally output Modbus RS485 bus digital signal or 4-20mA analog current signal at the same time.
The instrument is wall-mounted and wired, which is widely used in indoor construction projects.
◆It integrates detection and control functions, easy to use, stable and reliable technology;
◆ The CO2 sensor adopts NDIR infrared sensing technology, and the structure adopts the aluminum tube pass-through structure commonly used in analytical instruments, which ensures the excellent measurement performance of the product, and has the characteristics of more accurate measurement, faster response and more stable performance.
◆ The product shell size is 86×86×27mm, and the terminal block wiring box is 86 boxes, which is simple and convenient to install;
◆ Output signal: 1. A passive contact relay switch signal (standard) 2. Modbus RS485 digital signal (optional); 3. 4-20mA analog current signal (optional);
◆ Self-calibration function is turned on, and manual calibration in fresh air is supported.
|
Item |
Description |
Note: |
|
Operating voltage |
12-24VDC (standard) |
|
|
Detect objects |
CO2 gas in the air |
Optional temperature and humidity detection |
|
Detection method |
Free Diffusion |
|
|
sensors |
Infrared sensing principle |
High measurement accuracy and fast response speed |
|
Installation method: |
Wall mounted, wall mounted |
Installation is 1.5-2.0 meters from the ground |
|
Wiring method |
terminal blocks |
The terminal block is wired into the 86 box |
|
Detect Measuring range |
Carbon Dioxide: 0-5000ppm (standard) |
Other assays Measuring range can be customized |
|
Accuracy |
carbon dioxide:±30ppm +3%F.S |
20°C, 40%-70%RH environment |
|
Resolution |
CO2:1ppm |
|
|
Output signal |
1. Passive contact relay signal, load 3A (standard) 2. Modbus RS485 digital signal (optional) 3. 4-20mA analog current signal (optional) |
|
|
Power |
Approximately 3.0W (instantaneous), average 0.9W |
|
|
Response time |
T90 < 60 seconds |
|
|
Working conditions |
0~50°C Relative Humidity≤95%RH (no condensing) |
|
|
Product life |
Under normal use conditions, 3-5 years are expected |
|
|
Shape and size |
86mm×86mm×27mm |
|
|
Explosion-proof type |
Non-explosion-proof |
|
|
Quality |
150g |
|
|
Factory configuration |
Random attachments include: instruments, instructions, certificates |
|
|
Certification |
CE certified, Passed the ISO9001 quality management system certification in accordance with GB/T19001-2016/ISO9001:2015 standard |
|
|
HT-86-
|
|
Description |
|
I |
4-20mA current output |
|
|
RS |
RS485 output |
It is widely used in the detection and control of carbon dioxide gas concentration in indoor and mild environments: office buildings, hotels, hospitals, shopping malls, conference rooms, student classrooms, residential buildings, gymnasiums, computer rooms, underground parking lots, etc.