| Item | Specification |
|---|---|
| Target gas & range | Specialty VOC (UltraRAE / PGM-7200, discontinued) |
| Type | UltraRAE |
| Output & alarms | PID 10.6 eV unless a specialty lamp is specified; isobutylene span; lamp/electrode dislike oil mist |
| Protection & Ex | Portable IP65-class; IS nameplate |
| Operating temperature | Typically −20 to +50 °C |
| Certificates / acceptance | RAE Systems / Honeywell. IECEx/ATEX on the plate. A GB scan is not equivalent. |
From RAE Systems / Honeywell published data. Nameplate wins. Discontinued SKUs kept for old links.
UltraRAE is a handheld PID detector specifically designed for special organic gas detection in hazardous environments. It uses a photoionization detector (PID) with a 9.8eV, 10.6eV, or 11.7eV gas discharge lamp to separate the components to be measured in combination with a unique RAE-SEP gas separator tube for more targeted detection, or as a specialized separator tube for total volatile organic compounds (TVOC) as a broad-spectrum VOC detector.
• Compact and lightweight
• Built-in powerful suction pump
• High-volume data acquisition
• Large capacity rechargeable battery for long use
Dimensions: 23.5×7.6×5.1 cm
Weight: 567g (with rechargeable battery)
Sampling method: pump suction type
Shell material: engineering plastic, rubber jacket
Ingress protection: IP55, water and dust resistant
Resistance to electromagnetic radiation: EMI/RF rating: EMC Directive 89/336/EEC
Operating temperature: -20℃ ~ 45℃
Ambient Humidity: 0% ~ 95% Relative Humidity (Non-Condensing)
ATEX certified: EEx ia IIC T4
UL/cUL/CSA Certifications: Class I, Division 1, Group A, B, C, D
Display: Single line 8 characters 5×7 dot matrix LCD display, automatic background light
Display language: English + symbols
Display Value: Real-time detection value, TWA value, STEL value, peak value, battery voltage
Buttons: 1 operation key, 2 function keys
Alarm Style: 90dB@10cm buzzer and LED red light flash alarm
Alarm signals: gas exceeding the standard, battery voltage is insufficient, sensor failure, battery power is low alarm
Alarm point setting: Set the high/low alarm limit separately
Data storage: Built-in data capacity for storing 4000 points, including time, serial number, user ID, detection point ID, etc
Sampling interval: 1-3600 seconds adjustable
Data Communication: Communicates with the computer via RS232 interface
Sampling pump flow rate: 450~550cc/min
Battery: Rechargeable NiMH/NiCd battery or alkaline battery compartment
Operating time: 10 hours of continuous operation (depending on the working environment and frequency of use)
Charging time: 10 hours
Calibration method: zero/extended calibration
Sensor configuration: PID detector with 9.8 eV (optional 10.6/11.7 eV) UV lamp as standard
Sensor Parameters:
Detection Type Detection Range UV Lamp Type Resolution Response time(T90)
——————————————————————————————————
It is suitable for industrial safety monitoring and on-site inspection scenarios.