MIDAS S2-I-CH2 | Honeywell Midas® difluoromethane (S2 IR) ppm CH₂F₂

MIDAS S2-I-CH2 is a Honeywell Midas® IR cartridge for difluoromethane (S2 IR) (CH₂F₂), range ppm CH₂F₂, Midas S2 IR. It plugs into the MIDAS-T-004 extractive transmitter — not a Sensepoint XCD diffusion head. Sample line up to 30 m FEP at ~500 mL/min.

MIDAS S2-I-CH2 Honeywell Midas difluoromethane (S2 IR)

Mechanical & wiring figures

Product view (datasheet)
Product view (datasheet)
Outline dimensions
Outline dimensions
Main chassis
Main chassis
Terminal wiring
Terminal wiring

Part-number decode

SegmentMeaningThis SKU
MIDASHoneywell Midas® extractiveMIDAS
CH2difluoromethane (S2 IR)CH2
S2Midas S2 IR generationS2

Specifications

CategoryIR cartridge
GasCH₂F₂ / difluoromethane (S2 IR)
Rangeppm CH₂F₂
PrincipleMidas S2 IR
Flowapprox. 500 mL/min
Sample length2–30 m FEP
Supply24 VDC or PoE 48 V
Outputs0–21 mA + 3 relays + Modbus TCP/PoE
Temperature0–40 °C (0–30 °C with pyrolyzer)
Size / mass150×65×153 mm / 0.8 kg
ApprovalsCE, EN 50270, UL 61010-1, IEEE 802.3af

Transmitter 150×65×153 mm / 0.8 kg; NF₃ pyrolyzer 70×63×85 mm / 0.41 kg; high-temp PFC pyrolyzer 100×101×140 mm / 1.36 kg.

Why this SKU

Midas is extractive: the cell sits in the tool cabinet while FEP pulls sample from the valve box. difluoromethane (S2 IR) uses Midas S2 IR. Pyrolyzed species need MIDAS-T-00P / T-HTP / T-NP1 or the cartridge will not read.

Mates and spares

MIDAS S2-I-CH2 mates to MIDAS-T-004. Pump MIDAS-A-007, internal filter MIDAS-A-009. Do not substitute an electrochemical cartridge for this IR cell. Calibration notes live on product-2679.

Typical applications

Gas cabinets, VMBs, wet benches and CVD/etch exhaust. MIDAS S2-I-CH2 locks gas and cartridge life; budget transmitter, pump A-007 and internal filter A-009 on the PM cycle.

Compare

P/NTypeGasRange
MIDAS-T-004Extractive transmitterMIDAS-T-004
MIDAS-I-CO2IR cartridgeCO₂0–2.0 %vol
MIDAS-I-SF6IR cartridgeSF₆ppm SF₆
MIDAS S2-I-CH3IR cartridgeCH₃Fppm CH₃F
MIDAS S2-I-CO2IR cartridgeCO₂0–2.0 %vol
MIDAS S2-I-SF6IR cartridgeSF₆ppm SF₆
MIDAS-I-COSIR cartridgeCOSppm COS

Midas family matrix

Install and sample line

Wall-mount MIDAS-T-004 on the pre-drilled chassis or DIN kit A-036, then insert MIDAS S2-I-CH2. Sample 1/8″ID×1/4″OD FEP to 30 m; exhaust 1/4″ID×3/8″OD to 30 m. End-of-line filter 0780248 or 1830-0055/0027 by gas. 24 VDC (−15%/+10%) or PoE 48 V; pyrolyzer load up to 12.95 W. 0–40 °C, 0–30 °C with pyrolyzer.

FAQ

Can MIDAS S2-I-CH2 plug into Sensepoint XCD?
No. Midas is an extractive cartridge; XCD is a diffusion sensor housing. They do not mate.
Does MIDAS S2-I-CH2 need a pyrolyzer?
Gases marked ** (CH₂F₂, C₄F₆, C₅F₈, NF₃, CH₃F) need MIDAS-T-00P / T-HTP / T-NP1 plus a ventilated cover.
How is 4–20 mA landed on MIDAS S2-I-CH2?
3-wire sink, 3-wire source or 4-wire isolated 0–21 mA; plus 3 relays and Modbus TCP / PoE. Max 14 AWG.