MIDAS-T-NP1 | Honeywell Midas® Pyrolyzer module
MIDAS-T-NP1 is a Honeywell Midas® Pyrolyzer module. NP1 pyrolyzer for NF₃ and PFCs. XHF for NF₃/CH₃F; XCF for C₄F₆/C₅F₈/CH₂F₂. Supplied against MIDAS-A-001 / MIDASA001.

Mechanical & wiring figures




Part-number decode
| Segment | Meaning | This SKU |
|---|---|---|
| MIDAS | Honeywell Midas® extractive | MIDAS |
| T | transmitter / pyrolyzer / LonWorks | T |
| NP1 | NP1 pyrolyzer for NF₃ and PFCs. XHF for NF₃/CH₃F; XCF for C₄F₆/C₅F₈/CH₂F₂. | NP1 |
Specifications
| Category | Pyrolyzer module |
|---|---|
| Gas | Pyrolyzer module |
| Range | — |
| Principle | NP1 pyrolyzer for NF₃ and PFCs. XHF for NF₃/CH₃F; XCF for C₄F₆/C₅F₈/CH₂F₂. |
| Flow | approx. 500 mL/min |
| Sample length | 2–30 m FEP |
| Supply | 24 VDC or PoE 48 V |
| Outputs | 0–21 mA + 3 relays + Modbus TCP/PoE |
| Temperature | 0–40 °C (0–30 °C with pyrolyzer) |
| Size / mass | 150×65×153 mm / 0.8 kg |
| Approvals | CE, EN 50270, UL 61010-1, IEEE 802.3af |
Transmitter 150×65×153 mm / 0.8 kg; NF₃ pyrolyzer 70×63×85 mm / 0.41 kg; high-temp PFC pyrolyzer 100×101×140 mm / 1.36 kg.
Why this SKU
The extractive platform splits transmitter, pump, filters and pyrolyzer so XCD diffusion spares are not used on a Midas sample line. MIDAS-T-NP1 covers this segment only.
Mates and spares
Transmitter family MIDAS-T-004. Pump A-007, internal filter A-009, DIN A-036, pyrolyzer cover A-039/A-103. See product-2679.
Typical applications
Semiconductor gas cabinets, VMBs and tool chases. After the transmitter is on the wall, swap pump and filters on the §9.2 / §9.4 interval.
Compare
| P/N | Type | Gas | Range |
|---|---|---|---|
| MIDAS-T-004 | Extractive transmitter | MIDAS-T-004 | — |
| MIDAS-T-00P | Pyrolyzer module | MIDAS-T-00P | — |
| MIDAS-T-HTP | Pyrolyzer module | MIDAS-T-HTP | — |
| MIDAS-A-103 | Mounting accessory | MIDAS-A-103 | — |
Install and sample line
Pre-drilled wall mount, optional L-bracket A-032 or DIN A-036. 24 VDC or PoE. Sample and exhaust ports sit under the chassis — tube before power.
FAQ
- Can MIDAS-T-NP1 plug into Sensepoint XCD?
- No. Midas is an extractive cartridge; XCD is a diffusion sensor housing. They do not mate.
- Does MIDAS-T-NP1 need a pyrolyzer?
- Gases marked ** (CH₂F₂, C₄F₆, C₅F₈, NF₃, CH₃F) need MIDAS-T-00P / T-HTP / T-NP1 plus a ventilated cover.
- Is MIDAS-T-NP1 a complete detector?
- No. It bolts onto a universal extractive transmitter and takes power from that transmitter.
- How is 4–20 mA landed on MIDAS-T-NP1?
- 3-wire sink, 3-wire source or 4-wire isolated 0–21 mA; plus 3 relays and Modbus TCP / PoE. Max 14 AWG.
Documents
Datasheet PDF · Chinese manual · English technical manual · Midas family matrix
Quote and lead time
Stock and lead time are batch-based. If an E cartridge is short, look at the same-gas S cartridge. Pyrolyzed gases need the pyrolyzer ordered with the transmitter.