Honeywell XNX XNX-AMAE-RNNNN – no sensor (transmitter body), EC, ATEX, Aluminium, M25

XNX-AMAE-RNNNN is a Honeywell XNX EC-personality transmitter body, ATEX / IECEx (INMETRO on selected MPD SKUs), 4 × M25, LM25 aluminium (painted), 3 relays + 4–20 mA HART, no local HART port, no cell. Toxic and oxygen XNX electrochemical sensors mate here; catalytic LEL and MPD IR do not.

Same sensor, swap enclosure/approval: aluminium XNX-AMAE-RNNNN, 316SS XNX-AMSE-RNNNN, other approval XNX-UTAE-RNNNN. XNX-AMAE-RNNNN · XNX-AMSE-RNNNN · XNX-UTAE-RNNNN

XNX-AMAE-RNNNN Honeywell XNX sensor not fitted Aluminium M25

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULA
M / TEntry M=M25; T=3/4" NPTM
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECE
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBR
N / HLocal HART port N=no; H=yesN
NNNno sensor (transmitter body)NNN

Same sensor, swap enclosure/approval: aluminium XNX-AMAE-RNNNN, 316SS XNX-AMSE-RNNNN, other approval XNX-UTAE-RNNNN.

Technical specifications

Category变送器本体
PersonalityEC personality (toxic / oxygen electrochemical)
Sensor / rangeno sensor (transmitter body)
Targetbody / sensor not fitted
Principlepersonality board only
Output3 relays + 4–20 mA HART
Local HARTno local HART port
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × M25
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsATEX / IECEx (INMETRO on selected MPD SKUs)
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withXNX electrochemical toxic and oxygen cells

Why this personality / sensor

Electrochemical cells need bias, temperature compensation and a different connector than the mV MPD. This personality is the XNX answer to H₂S, CO, O₂, Cl₂ and other toxics on the XNX EC list. Do not buy it to run a pellistor.

Personality and replaceable parts

XNX-AMAE-RNNNN uses the EC personality (toxic / oxygen electrochemical) board and mates with XNX electrochemical toxic and oxygen cells. This SKU ships without a sensor; order the head by gas. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Water-treatment H₂S, boiler-house CO, nitrogen-purge O₂ and chlorine rooms keep the transmitter on the wall and swap EC cells on a 12–24 month cycle. The body SKU is what you stock when the gas list is still being written.

Selection contrast

P/NGasRangeOptionBody
XNX-AMSE-RNNNNbody—Relays316SS
XNX-UTAE-RNNNNbody—RelaysAluminium
XNX-AMAE-NNNNNbody—HARTAluminium
XNX-AMAE-MNNNNbody—ModbusAluminium
XNX-AMAE-FNNNNbody—FFBAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-AMAE-RNNNN (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × M25 entries—glands must match; do not retap XNX-AMAE-RNNNN. Land XNX-AMAE-RNNNN 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-AMAE-RNNNN lid stay non-intrusive. XNX-AMAE-RNNNN is a body: wall-mount the transmitter first and mate the head after the personality is confirmed—do not buy a configured SKU until the gas is frozen.

FAQ

Lead time?
Lot-based.
Enquiry?
Quote full P/N XNX-AMAE-RNNNN plus sensor/enclosure/approval.
Documents?
Manual links on SKU/hub pages.
Install?
Torque, entries and earthing per the manual.
What do the three relays on XNX-AMAE-RNNNN do?
XNX-AMAE-RNNNN adds three configurable relays on top of 4–20 mA HART—typically A1/A2/fault. It is not Modbus; bus siblings are XNX-AMAE-MNNNN / XNX-AMAE-FNNNN.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Availability: Not in stock — orders accepted; lead time approx. 16 weeks. Quote full P/N XNX-AMAE-RNNNN, gas/range and approval.