Honeywell XNX XNX-AMSV-NNIF1 – MPD IR propane 0–100 %LEL, mV, ATEX, 316SS, M25

XNX-AMSV-NNIF1 is a factory-configured Honeywell XNX with MPD infrared propane 0–100 %LEL, mV personality, ATEX / IECEx (INMETRO on selected MPD SKUs), 4 × M25, 316 stainless steel, 4–20 mA HART only (no option board), no local HART port. Order it for LPG bullets and cylinder halls; methane IR (IV1) will under-read propane.

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-NNIF1, 316SS XNX-AMSV-NNIF1, other approval XNX-UTSV-NNIF1. XNX-AMAV-NNIF1 · XNX-AMSV-NNIF1 · XNX-UTSV-NNIF1

XNX-AMSV-NNIF1 Honeywell XNX propane 316SS M25

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULA
M / TEntry M=M25; T=3/4" NPTM
A / SEnclosure A=aluminium; S=316SSS
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBN
N / HLocal HART port N=no; H=yesN
IF1MPD IR propane 0–100 %LELIF1

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-NNIF1, 316SS XNX-AMSV-NNIF1, other approval XNX-UTSV-NNIF1.

Technical specifications

CategoryTransmitter Configured
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeMPD IR propane 0–100 %LEL
TargetC₃H₈ / propane
PrincipleMPD infrared (propane)
Output4–20 mA HART only (no option board)
Local HARTno local HART port
Supply16–32 VDC (24 VDC nominal)
Enclosure316 stainless steel
Entries4 × M25
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsATEX / IECEx (INMETRO on selected MPD SKUs)
Temperature−40~+65 ℃
Massapprox. 5.0 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

Propane is heavier than air and slides into pits. MPD IR tuned for C₃ does not need oxygen and ignores silicone poisons that kill CB1 beads. Mount 200–400 mm above grade at the pit lip, not on the roof.

Personality and replaceable parts

XNX-AMSV-NNIF1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD IR propane 0–100 %LEL. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

LPG tank farms, bottle-filling halls and kitchen-gas manifolds need a propane-specific IR trip. XNX hard-wires 4–20 mA HART to tank ESD; a handheld only proves the aisle you walked.

Selection contrast

P/NGasRangeOptionBody
XNX-AMAV-NNIF1C₃H₈0–100 %LELHARTAluminium
XNX-UTSV-NNIF1C₃H₈0–100 %LELHART316SS
XNX-AMSV-NNCB1LEL0–100 %LELHART316SS
XNX-AMSV-NNIV1CH₄0–100 %LELHART316SS
XNX-AMSV-NNIC1CO₂0–5 %v/vHART316SS
XNX-AMSV-NNNNNbodyHART316SS
XNX-AMSV-RNIF1C₃H₈0–100 %LELRelays316SS

XNX family matrix

Installation and wiring

Wall-mount XNX-AMSV-NNIF1 (316 stainless steel, approx. 5.0 kg) on a rigid stand sized for that mass. This SKU uses 4 × M25 entries—glands must match; do not retap XNX-AMSV-NNIF1. Land XNX-AMSV-NNIF1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-AMSV-NNIF1 lid stay non-intrusive. XNX-AMSV-NNIF1 propane belongs at the pit lip, not the roof.

FAQ

Can I use methane IR instead of XNX-AMSV-NNIF1 on an LPG skid?
No. Response curves differ. XNX-AMSV-NNIF1 is propane (IF1). IV1 methane IR will under-alarm a propane release.
Does XNX-AMSV-NNIF1 work in oxygen-free LPG vapour space?
Yes. MPD IR on XNX-AMSV-NNIF1 does not combust the sample, so inerted LPG vapour spaces remain measurable.
Why is XNX-AMSV-NNIF1 316SS instead of aluminium?
XNX-AMSV-NNIF1 is the marine/sour-service body (~5 kg). Inland dry rooms can take aluminium sibling XNX-AMAV-NNIF1 and save mass on the bracket.
Can I convert XNX-AMSV-NNIF1 from ATEX M25 to NPT in the field?
No. XNX-AMSV-NNIF1 flameproof entries are machined M25. North-American NPT is UL sibling XNX-UTSV-NNIF1, not an adaptor on this ATEX body.
Does XNX-AMSV-NNIF1 include alarm relays?
No. XNX-AMSV-NNIF1 is 4–20 mA HART only. Local trip contacts need option-R sibling XNX-AMSV-RNIF1; plant-bus needs Modbus XNX-AMSV-MNIF1 or Foundation Fieldbus XNX-AMSV-FNIF1.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Stock is lot-based. If this box is out, jump to 316SS XNX-AMSV-NNIF1 or UL XNX-UTSV-NNIF1 rather than a dead SKU.