Honeywell XNX XNX-AMSV-RHCB1 – MPD catalytic 0–100 %LEL, mV, ATEX, 316SS, M25

XNX-AMSV-RHCB1 is a factory-configured Honeywell XNX gas detector: mV personality, MPD catalytic bead 0–100 %LEL, ATEX / IECEx (INMETRO on selected MPD SKUs), 4 × M25, 316 stainless steel, 3 relays + 4–20 mA HART, local HART port on the transmitter. Specify it for mixed hydrocarbon LEL points where infrared windows would fog or the stream is not methane/propane-specific.

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-RHCB1, 316SS XNX-AMSV-RHCB1, other approval XNX-UTSV-RHCB1. XNX-AMAV-RHCB1 · XNX-AMSV-RHCB1 · XNX-UTSV-RHCB1

XNX-AMSV-RHCB1 Honeywell XNX flammable gas (catalytic) 316SS M25

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULA
M / TEntry M=M25; T=3/4" NPTM
A / SEnclosure A=aluminium; S=316SSS
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBR
N / HLocal HART port N=no; H=yesH
CB1MPD catalytic 0–100 %LELCB1

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-RHCB1, 316SS XNX-AMSV-RHCB1, other approval XNX-UTSV-RHCB1.

Technical specifications

CategoryTransmitter Configured
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeMPD catalytic 0–100 %LEL
TargetLEL / flammable gas (catalytic)
PrincipleMPD catalytic bead
Output3 relays + 4–20 mA HART
Local HARTlocal HART port on the transmitter
Supply16–32 VDC (24 VDC nominal)
Enclosure316 stainless steel
Entries4 × M25
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsATEX / IECEx (INMETRO on selected MPD SKUs)
Temperature−40~+65 ℃
Massapprox. 5.0 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

A poison-resistant MPD pellistor sees combustion heat across a wide hydrocarbon mix, including species an IR filter misses. It needs oxygen and hates silicones. Mount above light-gas releases and below heavy vapours; keep silicone sealants off the sinter.

Personality and replaceable parts

XNX-AMSV-RHCB1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD catalytic 0–100 %LEL. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Pump rooms, filling gantries and compressor packages still standardise on catalytic LEL because the gas slate is mixed. XNX holds 4–20 mA HART into the ESD matrix; magnetic non-intrusive calibration keeps the flameproof lid closed.

Selection contrast

P/NGasRangeOptionBody
XNX-AMAV-RHCB1LEL0–100 %LELRelaysAluminium
XNX-UTSV-RHCB1LEL0–100 %LELRelays316SS
XNX-AMSV-RHIV1CH₄0–100 %LELRelays316SS
XNX-AMSV-RHIF1C₃H₈0–100 %LELRelays316SS
XNX-AMSV-RHIC1CO₂0–5 %v/vRelays316SS
XNX-AMSV-RHNNNbody—Relays316SS
XNX-AMSV-NHCB1LEL0–100 %LELHART316SS

XNX family matrix

Installation and wiring

Wall-mount XNX-AMSV-RHCB1 (316 stainless steel, approx. 5.0 kg) on a rigid stand sized for that mass. This SKU uses 4 × M25 entries—glands must match; do not retap XNX-AMSV-RHCB1. Land XNX-AMSV-RHCB1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-AMSV-RHCB1 lid stay non-intrusive. Keep silicones off the XNX-AMSV-RHCB1 pellistor; light hydrocarbons high, heavy vapours low.

FAQ

Calibration?
Per fitted sensor and target gas.
Documents?
Manual links on SKU/hub pages.
Which line is XNX-AMSV-RHCB1?
Honeywell Sensepoint XNX universal gas transmitter.
Install?
Torque, entries and earthing per the manual.
Which sensors?
CAT/IR/EC etc. via personality/sensor configuration digits.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Availability: Not in stock — orders accepted; lead time approx. 16 weeks. Quote full P/N XNX-AMSV-RHCB1, gas/range and approval.

WhatsAppTop