Honeywell XNX XNX-UTAE-FNNNN – no sensor (transmitter body), EC, UL, Aluminium, 3/4" NPT

XNX-UTAE-FNNNN is a Honeywell XNX EC-personality transmitter body, UL / cUL, 4 × 3/4" NPT, LM25 aluminium (painted), Foundation Fieldbus + 4–20 mA HART, no local HART port, no cell. Toxic and oxygen XNX electrochemical sensors mate here; catalytic LEL and MPD IR do not.

Same sensor, swap enclosure/approval: aluminium XNX-UTAE-FNNNN, 316SS XNX-UTSE-FNNNN, other approval XNX-AMAE-FNNNN. XNX-UTAE-FNNNN · XNX-UTSE-FNNNN · XNX-AMAE-FNNNN

XNX-UTAE-FNNNN Honeywell XNX sensor not fitted Aluminium 3/4" NPT

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULU
M / TEntry M=M25; T=3/4" NPTT
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECE
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBF
N / HLocal HART port N=no; H=yesN
NNNno sensor (transmitter body)NNN

Same sensor, swap enclosure/approval: aluminium XNX-UTAE-FNNNN, 316SS XNX-UTSE-FNNNN, other approval XNX-AMAE-FNNNN.

Technical specifications

Category变送器本体
PersonalityEC personality (toxic / oxygen electrochemical)
Sensor / rangeno sensor (transmitter body)
Targetbody / sensor not fitted
Principlepersonality board only
OutputFoundation Fieldbus + 4–20 mA HART
Local HARTno local HART port
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × 3/4" NPT
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsUL / cUL
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withXNX electrochemical toxic and oxygen cells

Why this personality / sensor

Electrochemical cells need bias, temperature compensation and a different connector than the mV MPD. This personality is the XNX answer to H₂S, CO, O₂, Cl₂ and other toxics on the XNX EC list. Do not buy it to run a pellistor.

Personality and replaceable parts

XNX-UTAE-FNNNN uses the EC personality (toxic / oxygen electrochemical) board and mates with XNX electrochemical toxic and oxygen cells. This SKU ships without a sensor; order the head by gas. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Water-treatment H₂S, boiler-house CO, nitrogen-purge O₂ and chlorine rooms keep the transmitter on the wall and swap EC cells on a 12–24 month cycle. The body SKU is what you stock when the gas list is still being written.

Selection contrast

P/NGasRangeOptionBody
XNX-UTSE-FNNNNbody—FFB316SS
XNX-AMAE-FNNNNbody—FFBAluminium
XNX-UTAE-NNNNNbody—HARTAluminium
XNX-UTAE-RNNNNbody—RelaysAluminium
XNX-UTAE-MNNNNbody—ModbusAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-UTAE-FNNNN (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × 3/4" NPT entries—glands must match; do not retap XNX-UTAE-FNNNN. Land XNX-UTAE-FNNNN 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-UTAE-FNNNN lid stay non-intrusive. XNX-UTAE-FNNNN is a body: wall-mount the transmitter first and mate the head after the personality is confirmed—do not buy a configured SKU until the gas is frozen.

FAQ

Local HART?
Depends on the local-HART digit — do not confuse with other options.
Can I add an MPD sensor to XNX-UTAE-FNNNN later?
XNX-UTAE-FNNNN ships as a transmitter body. mV personalities accept MPD CB1/IV1/IF1/IC1 heads; IR personalities need Optima/Excel; EC personalities need XNX electrochemical cells. Do not mix those three families on this board.
Install?
Torque, entries and earthing per the manual.
Is XNX-UTAE-FNNNN the same as Modbus?
No. XNX-UTAE-FNNNN is Foundation Fieldbus. Modbus RTU is sibling XNX-UTAE-MNNNN. Both still carry 4–20 mA HART on XNX.
Spares?
Use the family matrix for heads and accessories.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Availability: Not in stock — orders accepted; lead time approx. 16 weeks. Quote full P/N XNX-UTAE-FNNNN, gas/range and approval.