Honeywell XNX XNX-UTAV-FHIC1 – MPD IR carbon dioxide 0–5 %v/v, mV, UL, Aluminium, 3/4" NPT

XNX-UTAV-FHIC1 is a factory-configured Honeywell XNX with MPD infrared carbon dioxide 0–5 %v/v, mV personality, UL / cUL, 4 × 3/4" NPT, LM25 aluminium (painted), Foundation Fieldbus + 4–20 mA HART, local HART port on the transmitter. Use it on beverage carbonation, inerting cabinets and fermenter headspace—not as a toxic ppm cell.

Same sensor, swap enclosure/approval: aluminium XNX-UTAV-FHIC1, 316SS XNX-UTSV-FHIC1, other approval XNX-AMAV-FHIC1. XNX-UTAV-FHIC1 · XNX-UTSV-FHIC1 · XNX-AMAV-FHIC1

XNX-UTAV-FHIC1 Honeywell XNX carbon dioxide Aluminium 3/4" NPT

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULU
M / TEntry M=M25; T=3/4" NPTT
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBF
N / HLocal HART port N=no; H=yesH
IC1MPD IR carbon dioxide 0–5 %v/vIC1

Same sensor, swap enclosure/approval: aluminium XNX-UTAV-FHIC1, 316SS XNX-UTSV-FHIC1, other approval XNX-AMAV-FHIC1.

Technical specifications

CategoryTransmitter Configured
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeMPD IR carbon dioxide 0–5 %v/v
TargetCO₂ / carbon dioxide
PrincipleMPD infrared (CO₂)
OutputFoundation Fieldbus + 4–20 mA HART
Local HARTlocal HART port on the transmitter
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × 3/4" NPT
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsUL / cUL
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

CO₂ is heavier than air and fills cellars from the floor up. Percent-level CO₂ is an IR measurement; an electrochemical toxic cell cannot span 5 %vol. Mount 300 mm above the lowest floor and keep the optical path off wet drains.

Personality and replaceable parts

XNX-UTAV-FHIC1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD IR carbon dioxide 0–5 %v/v. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Soft-drink carbonation, brewery cellars and CO₂-inerted cabinets need a 5 %vol trip before asphyxiation. XNX provides the hard-wired extract start; a portable wand is only a leak survey tool.

Selection contrast

P/NGasRangeOptionBody
XNX-UTSV-FHIC1CO₂0–5 %v/vFFB316SS
XNX-AMAV-FHIC1CO₂0–5 %v/vFFBAluminium
XNX-UTAV-FHCB1LEL0–100 %LELFFBAluminium
XNX-UTAV-FHIV1CH₄0–100 %LELFFBAluminium
XNX-UTAV-FHIF1C₃H₈0–100 %LELFFBAluminium
XNX-UTAV-FHNNNbody—FFBAluminium
XNX-UTAV-NHIC1CO₂0–5 %v/vHARTAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-UTAV-FHIC1 (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × 3/4" NPT entries—glands must match; do not retap XNX-UTAV-FHIC1. Land XNX-UTAV-FHIC1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-UTAV-FHIC1 lid stay non-intrusive. XNX-UTAV-FHIC1 5 %v/v CO₂ hugs the cellar floor.

FAQ

Calibration?
Per fitted sensor and target gas.
Install?
Torque, entries and earthing per the manual.
Comms options?
Relays, Modbus, Foundation Fieldbus etc. depending on order.
Enquiry?
Quote full P/N XNX-UTAV-FHIC1 plus sensor/enclosure/approval.
Documents?
Manual links on SKU/hub pages.