Honeywell XNX XNX-UTAV-RHCB1 – MPD catalytic 0–100 %LEL, mV, UL, Aluminium, 3/4" NPT

XNX-UTAV-RHCB1 is a factory-configured Honeywell XNX gas detector: mV personality, MPD catalytic bead 0–100 %LEL, UL / cUL, 4 × 3/4" NPT, LM25 aluminium (painted), 3 relays + 4–20 mA HART, local HART port on the transmitter. Specify it for mixed hydrocarbon LEL points where infrared windows would fog or the stream is not methane/propane-specific.

Same sensor, swap enclosure/approval: aluminium XNX-UTAV-RHCB1, 316SS XNX-UTSV-RHCB1, other approval XNX-AMAV-RHCB1. XNX-UTAV-RHCB1 · XNX-UTSV-RHCB1 · XNX-AMAV-RHCB1

XNX-UTAV-RHCB1 Honeywell XNX flammable gas (catalytic) Aluminium 3/4" NPT

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULU
M / TEntry M=M25; T=3/4" NPTT
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBR
N / HLocal HART port N=no; H=yesH
CB1MPD catalytic 0–100 %LELCB1

Same sensor, swap enclosure/approval: aluminium XNX-UTAV-RHCB1, 316SS XNX-UTSV-RHCB1, other approval XNX-AMAV-RHCB1.

Technical specifications

CategoryTransmitter Configured
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeMPD catalytic 0–100 %LEL
TargetLEL / flammable gas (catalytic)
PrincipleMPD catalytic bead
Output3 relays + 4–20 mA HART
Local HARTlocal HART port on the transmitter
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × 3/4" NPT
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsUL / cUL
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

A poison-resistant MPD pellistor sees combustion heat across a wide hydrocarbon mix, including species an IR filter misses. It needs oxygen and hates silicones. Mount above light-gas releases and below heavy vapours; keep silicone sealants off the sinter.

Personality and replaceable parts

XNX-UTAV-RHCB1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD catalytic 0–100 %LEL. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Pump rooms, filling gantries and compressor packages still standardise on catalytic LEL because the gas slate is mixed. XNX holds 4–20 mA HART into the ESD matrix; magnetic non-intrusive calibration keeps the flameproof lid closed.

Selection contrast

P/NGasRangeOptionBody
XNX-UTSV-RHCB1LEL0–100 %LELRelays316SS
XNX-AMAV-RHCB1LEL0–100 %LELRelaysAluminium
XNX-UTAV-RHIV1CH₄0–100 %LELRelaysAluminium
XNX-UTAV-RHIF1C₃H₈0–100 %LELRelaysAluminium
XNX-UTAV-RHIC1CO₂0–5 %v/vRelaysAluminium
XNX-UTAV-RHNNNbody—RelaysAluminium
XNX-UTAV-NHCB1LEL0–100 %LELHARTAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-UTAV-RHCB1 (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × 3/4" NPT entries—glands must match; do not retap XNX-UTAV-RHCB1. Land XNX-UTAV-RHCB1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-UTAV-RHCB1 lid stay non-intrusive. Keep silicones off the XNX-UTAV-RHCB1 pellistor; light hydrocarbons high, heavy vapours low.

FAQ

Alu/SS?
Choose by corrosion/weight; enclosure digit is in the P/N.
Which line is XNX-UTAV-RHCB1?
Honeywell Sensepoint XNX universal gas transmitter.
Documents?
Manual links on SKU/hub pages.
Spares?
Use the family matrix for heads and accessories.
Install?
Torque, entries and earthing per the manual.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Availability: Not in stock — orders accepted; lead time approx. 16 weeks. Quote full P/N XNX-UTAV-RHCB1, gas/range and approval.

WhatsAppTop