SPXCDALMG1
SPXCDALMG1 is the Sensepoint XCD Electrochemical (Surecell™) hydrogen complete transmitter, default 0-1000ppm, LM25 epoxy-coated aluminium, 2 × M20, ATEX / IECEx / GB.

Part-number matrix
| Segment | Meaning | This SKU |
|---|---|---|
| SPXCD | Sensepoint XCD series | SPXCD |
| A / U | Approval A=ATEX/IECEx/GB; U=UL | A |
| L / S | Enclosure L=LM25 aluminium; S=316SS | L |
| M / N | Entry M=M20; N=3/4″ NPT | M |
| G1 | hydrogen,Electrochemical (Surecell™) | G1 |
Key specifications
| Target gas | H₂ / hydrogen |
|---|---|
| Principle | Electrochemical (Surecell™) |
| Default range | 0-1000ppm |
| User FSD window | 0-1000ppm only |
| Resolution | n/a |
| Output | 4–20 mA sink/source + optional Modbus RTU |
| Supply | 16–32 VDC (24 VDC nominal) |
| Power | 3.7 W |
| Enclosure | LM25 epoxy-coated aluminium |
| Entries | 2 × M20 |
| Display | Tri-colour backlight LCD |
| Relays | 3×5A@250VAC |
| Ingress | IP66 |
| Approvals | ATEX / IECEx / GB |
| Temperature | −40~+65 ℃ |
| Mass | approx. 1.7 kg |
Why this principle
Fixed-point leak monitoring into a controller/ESD on 4–20 mA.
Typical applications
Fixed-point leak monitoring into a controller/ESD on 4–20 mA. Magnetic bump test without a hot-work permit.
Installation
Wall-mount SPXCDALMG1 through the one-piece plate with M8 bolts. Entries 2 × M20 — glands must match. Land 4–20 mA as three-wire. Magnetic wand calibration stays non-intrusive.
FAQ
- Is the safety function on SPXCDALMG1 the relays or 4–20 mA?
- On SPXCDALMG1 the only EN performance safety function is 4–20 mA. Relays and Modbus are not SIL/performance-certified.
- Is SPXCDALMG1 ATEX or UL certified?
- SPXCDALMG1 is the ATEX / IECEx / GB scheme. Do not use it as the other system.
- Does SPXCDALMG1 carry a China / GB certificate?
- SPXCDALMG1 literature states GB Ex d IIC T4 (GB3836); no standalone CNEx serial is published here.
- How do I calibrate SPXCDALMG1?
- Zero/span SPXCDALMG1 on the transmitter with certified gas and cap S3KCAL. Recalibrate after cartridge swap.
- How does SPXCDALMG1 differ from SPXCDASMG1?
- SPXCDALMG1 is complete kit (transmitter + cartridge), LM25 epoxy-coated aluminium, 2 × M20, ATEX / IECEx / GB. SPXCDASMG1 is the enclosure/approval/entry sibling.
- Does SPXCDALMG1 provide 4–20 mA?
- SPXCDALMG1 outputs 4–20 mA (source/sink). 4–20 mA is the only EN performance safety function.
- Is SPXCDALMG1 IP66?
- SPXCDALMG1 housing is IP66 (EN 60529). With weather cap and sinter down, IPX6 is kept.
- How is SPXCDALMG1 mounted?
- Wall-mount SPXCDALMG1 on the one-piece plate with M8 bolts; pipe Ø40–80 mm uses SPXCDMTBR, duct SPXCDDMK. Glands must match 2 × M20.
- Can I fit a different-gas cartridge on SPXCDALMG1?
- XCD auto-recognises the same family only. Do not mix an O₂ cell onto a flammable/toxic SPXCDALMG1 transmitter.
Downloads
Honeywell official technical manual and certificates are available from GZion as PDF.
Availability and enquiry
Availability:In stock. Quote full P/N SPXCDALMG1.