Honeywell Sensepoint XCD SPXCDALMPX – Fixed C₃H₈ Detector (0-100%LEL, Infrared (dual-beam), ATEX, LM25, M20)

SPXCDALMPX is the Sensepoint XCD infrared propane LEL transmitter, 0–100 %LEL, LM25 epoxy-coated aluminium, 2 × M20, ATEX / IECEx / GB. Order it for LPG bullet farms and cylinder filling halls where methane IR would under-read.

Same gas, swap enclosure/approval: aluminium SPXCDALMPX, 316SS SPXCDASMPX, UL SPXCDULNPX. SPXCDALMPX · SPXCDASMPX · SPXCDULNPX

SPXCDALMPX Honeywell Sensepoint XCD C3H8 detector LM25 M20

Part-number decode

SegmentMeaningThis SKU
SPXCDSensepoint XCD seriesSPXCD
A / UApproval A=ATEX/IECEx/GB; U=ULA
L / SEnclosure L=LM25 aluminium; S=316SSL
M / NEntry M=M20; N=3/4" NPTM
PXGas propane, Infrared (dual-beam)PX

Same gas, swap enclosure/approval: aluminium SPXCDALMPX, 316SS SPXCDASMPX, UL SPXCDULNPX.

Technical specifications

Target gasC₃H₈ / propane
PrincipleInfrared (dual-beam)
Default range0-100%LEL
User FSD window20-100%LEL
Resolution10%LEL
Output4–20 mA sink/source + optional Modbus RTU
Supply16–32 VDC (24 VDC nominal)
Power3.7 W
EnclosureLM25 epoxy-coated aluminium
Entries2 × M20
DisplayTri-colour backlight LCD
Relays3×5A@250VAC
IngressIP66
ApprovalsATEX / IECEx / GB
Temperature−40~+65 ℃
Massapprox. 2.0 kg (4.4 lb)

Why this principle for this gas

Propane is heavier than air and slides along floors toward pits. Dual-beam IR tuned for C₃ is used so a methane-calibrated pellistor or RX cell cannot hide a rich LPG layer. Mount 200–400 mm above grade, at the pit lip, not on the roof.

Sensor and replaceable parts

OEM cartridge SPXCDXSPXSS. Calibration cap S3KCAL. Collecting cone follows buoyancy—see installation. Pipe/duct kits: SPXCDMTBR / SPXCDDMK.

Typical applications

LPG tank farms, bottle-filling halls and kitchen-gas manifolds need a propane-specific IR trip. XCD gives a hard-wired 4–20 mA to the tank ESD; a handheld only proves the aisle you walked.

Selection contrast

P/NGasRangePrinciple
SPXCDALMPXC₃H₈0-100%LELIR
SPXCDALMRXCH₄0-100%LELIR
SPXCDALMFXLEL0-100%LELCatalytic bead
SPXCDALMB1CO₂0-2.00%VolIR
SPXCDASMPXC₃H₈0-100%LELIR
SPXCDULNPXC₃H₈0-100%LELIR

XCD family matrix

Installation and wiring

Wall-mount SPXCDALMPX (propane, LM25 epoxy-coated aluminium) through the one-piece plate with M8 bolts sized for that mass. This SKU uses 2 × M20 entries: pipe kit SPXCDMTBR covers Ø1.5–3″, duct kit is SPXCDDMK, and glands must match—do not retap SPXCDALMPX. Land SPXCDALMPX 4–20 mA as three-wire and set Modbus address from the menu only. Magnetic wand calibration on the SPXCDALMPX lid stays non-intrusive. SPXCDALMPX propane belongs at the pit lip, not the roof.

FAQ

SPXCDALMPX: Can I use methane IR (RX) on an LPG skid?
SPXCDALMPX — No. Response curves differ. Specify PX or you will under-alarm a propane release.
SPXCDALMPX: Does PX work in oxygen-free vapour spaces?
SPXCDALMPX — Yes. IR does not combust the sample, so inerted LPG vapour spaces remain measurable.
LM25 or 316SS for SPXCDALMPX (propane)?
SPXCDALMPX ships in LM25 epoxy aluminium (~4.4 lb). For propane in salt spray, caustic CIP or sour-water splash, switch to 316SS sibling SPXCDASMPX instead of painting this lid.
Can I convert SPXCDALMPX from ATEX M20 to NPT in the field?
No. SPXCDALMPX flameproof entries are machined M20. North-American NPT is UL sibling SPXCDULNPX, not an adaptor on this ATEX propane body.
Can I retrofit Modbus on SPXCDALMPX after it ships?
Modbus RTU on SPXCDALMPX is a transmitter sales option, not a jumper on the propane lid. Confirm the option before the box leaves; 4–20 mA sink/source is already on this SKU.