Honeywell Sensepoint XCD SPXCDULNRX – Fixed CH₄ Detector (0-100%LEL, Infrared (dual-beam), UL, LM25, 3/4" NPT)

SPXCDULNRX is the dual-beam infrared methane LEL point on Sensepoint XCD, 0–100 %LEL, LM25 epoxy-coated aluminium, 2 × 3/4" NPT, UL / CSA. It is the SKU for gas-transmission compounds and biogas roofs where catalytic poison or oxygen-free streams rule out a pellistor.

Same gas, swap enclosure/approval: aluminium SPXCDALMRX, 316SS SPXCDASMRX, UL SPXCDULNRX. SPXCDALMRX · SPXCDASMRX · SPXCDULNRX

SPXCDULNRX Honeywell Sensepoint XCD CH4 detector LM25 3/4" NPT

Part-number decode

SegmentMeaningThis SKU
SPXCDSensepoint XCD seriesSPXCD
A / UApproval A=ATEX/IECEx/GB; U=ULU
L / SEnclosure L=LM25 aluminium; S=316SSL
M / NEntry M=M20; N=3/4" NPTN
RXGas methane, Infrared (dual-beam)RX

Same gas, swap enclosure/approval: aluminium SPXCDALMRX, 316SS SPXCDASMRX, UL SPXCDULNRX.

Technical specifications

Target gasCH₄ / methane
PrincipleInfrared (dual-beam)
Default range0-100%LEL
User FSD window20-100%LEL
Resolution10%LEL
Output4–20 mA sink/source + optional Modbus RTU
Supply16–32 VDC (24 VDC nominal)
Power3.7 W
EnclosureLM25 epoxy-coated aluminium
Entries2 × 3/4" NPT
DisplayTri-colour backlight LCD
Relays3×5A@250VAC
IngressIP66
ApprovalsUL / CSA
Temperature−40~+65 ℃
Massapprox. 2.0 kg (4.4 lb)

Why this principle for this gas

Methane is lighter than air and rises to roof vents and canopy corners. Dual-beam IR is used because it does not need oxygen and ignores silicone poisons that kill catalytic beads. Mount high, under the eaves or at the compressor hall ridge, and keep the optical window out of direct wash-down.

Sensor and replaceable parts

OEM cartridge SPXCDXSRXSS. Calibration cap S3KCAL. Collecting cone follows buoyancy—see installation. Pipe/duct kits: SPXCDMTBR / SPXCDDMK.

Typical applications

City-gate stations, LNG boil-off rooms and anaerobic digester roofs need a methane-specific IR point. XCD holds the trip while operators stay outside the classified shed—something a portable survey cannot guarantee.

Selection contrast

P/NGasRangePrinciple
SPXCDULNRXCH₄0-100%LELIR
SPXCDULNPXC₃H₈0-100%LELIR
SPXCDULNFXLEL0-100%LELCatalytic bead
SPXCDULNB1CO₂0-2.00%VolIR
SPXCDALMRXCH₄0-100%LELIR
SPXCDASMRXCH₄0-100%LELIR

XCD family matrix

Installation and wiring

Wall-mount SPXCDULNRX (methane, LM25 epoxy-coated aluminium) through the one-piece plate with M8 bolts sized for that mass. This SKU uses 2 × 3/4" NPT entries: pipe kit SPXCDMTBR covers Ø1.5–3″, duct kit is SPXCDDMK, and glands must match—do not retap SPXCDULNRX. Land SPXCDULNRX 4–20 mA as three-wire and set Modbus address from the menu only. Magnetic wand calibration on the SPXCDULNRX lid stays non-intrusive. Park the SPXCDULNRX methane IR at the ridge and out of wash-down.

FAQ

SPXCDULNRX: Does the RX IR cell see propane?
SPXCDULNRX — Poorly. Propane has its own PX SKU. Do not substitute RX on an LPG skid.
SPXCDULNRX: Why not use catalytic LEL for methane?
SPXCDULNRX — If the stream can be inert or silicone-contaminated, the pellistor goes to sleep. IR keeps working at 0 % oxygen.
LM25 or 316SS for SPXCDULNRX (methane)?
SPXCDULNRX ships in LM25 epoxy aluminium (~4.4 lb). For methane in salt spray, caustic CIP or sour-water splash, switch to 316SS sibling SPXCDASMRX instead of painting this lid.
Why is SPXCDULNRX NPT instead of M20?
SPXCDULNRX is the UL/CSA methane body and ships 3/4" NPT. Do not tap M20 on this lid—order ATEX sibling SPXCDALMRX if metric glands are mandatory.
Can I retrofit Modbus on SPXCDULNRX after it ships?
Modbus RTU on SPXCDULNRX is a transmitter sales option, not a jumper on the methane lid. Confirm the option before the box leaves; 4–20 mA sink/source is already on this SKU.

Documents

Honeywell Sensepoint XCD datasheet / manual · On-site XCD selection matrix

Availability and enquiry

Stock is lot-based. If this aluminium ATEX box is out, jump to 316SS SPXCDASMRX or UL SPXCDULNRX rather than a dead SKU.