Honeywell Sensepoint XCD Sensor Cartridges
Replaceable sensor cartridges (SPXCDXS*SS): catalytic, IR, electrochemical for flammable, CH4, C3H8, O2, H2S, CO, H2, NO2, CO2.

Part-number matrix
| P/N | Type | Description |
|---|---|---|
| SPXCDXSFXSS | Sensor cartridge | Fixed combustible gas sensor, XCD |
| SPXCDXSRXSS | Sensor cartridge | Fixed infrared methane (CH4) sensor, XCD |
| SPXCDXSPXSS | Sensor cartridge | Fixed infrared propane (C3H8) sensor, XCD |
| SPXCDXSO1SS | Sensor cartridge | Fixed oxygen (O2) sensor, XCD |
| SPXCDXSHXSS | Sensor cartridge | Fixed hydrogen sulfide (H2S) sensor, XCD |
| SPXCDXSCXSS | Sensor cartridge | Fixed carbon monoxide (CO) sensor, XCD |
| SPXCDXSG1SS | Sensor cartridge | Fixed hydrogen (H2) sensor, XCD |
| SPXCDXSNXSS | Sensor cartridge | Fixed nitrogen dioxide (NO2) probe, XCD |
| SPXCDXSB1SS | Sensor cartridge | Fixed carbon dioxide (CO2) sensor, XCD |
| SPXCDXSB2SS | Sensor cartridge | Fixed carbon dioxide (CO2) sensor, XCD |
Why this principle
SPXCDXS*SS cartridges are pre-calibrated and plug-and-play: the transmitter auto-recognizes the cartridge, hot-swap replacement needs no special tools. When a sensor reaches end of life you replace only the cartridge — not the whole instrument — cutting spares cost and downtime. One transmitter accepts catalytic, electrochemical (SureCell) and IR cartridges.
Key specifications
| Gas | Principle | Range | Cal point | T90 | Accuracy | Op. temp | Default alarm A1/A2 |
|---|---|---|---|---|---|---|---|
| Oxygen O2 | EC | 25.0%Vol | 20.9%Vol (air) | <30 s | <±0.5%Vol | -20~+55℃ | 19.5%Vol ↓ / 23.5%Vol ↑ |
| Hydrogen sulfide H2S | EC | 10.0–100.0 ppm (def. 50) | 25 ppm | <50 s | <±1 ppm | -20~+55℃ | 10 ppm / 20 ppm |
| Carbon monoxide CO | EC | 100–1000 ppm (def. 300) | 100 ppm | <30 s | <±6 ppm | -20~+55℃ | 30 ppm / 100 ppm |
| Hydrogen H2 | EC | 1000 ppm | 500 ppm | <65 s | <±25 ppm | -20~+55℃ | 200 ppm / 400 ppm |
| Nitrogen dioxide NO2 | EC | 10.0–50.0 ppm (def. 10) | 5 ppm | <40 s | <±3 ppm | -20~+55℃ | 5 ppm / 10 ppm |
| Flammable (catalytic) | Cat. bead | 20–100%LEL (def. 100) | 50%LEL | <25 s | <±1.5%LEL | -20~+55℃ | 20%LEL / 40%LEL |
| Methane CH4 (IR) | IR | 20–100%LEL | 50%LEL | <30 s | <±1.5%LEL | -20~+50℃ | 20%LEL / 40%LEL |
| Propane C3H8 (IR) | IR | 20–100%LEL | 50%LEL | <30 s | <±1%LEL | -20~+50℃ | 20%LEL / 40%LEL |
| Carbon dioxide CO2 (IR) | IR | 2%Vol | 1%Vol | <30 s | <±0.04%Vol | -20~+50℃ | 0.4%Vol / 0.8%Vol |
Installation
Replacement: power down (or confirm the area is safe), unscrew the old cartridge, plug in the new one — gas type and range are recognized automatically. Then run zero and span calibration from the magnetic-wand menu. Recommended cal gas: clean air (20.9%Vol) for O2; 25 ppm H2S; 100 ppm CO; 500 ppm H2; 5 ppm NO2; 50%LEL for flammables; 1%Vol for CO2. EC cartridges work at -20 ~ +55 °C, IR at -20 ~ +50 °C.
Calibration notes & sensor life
Warm up 30 minutes before calibration. Zero gas (air/N2) 0.5–1.0 L/min, flammable span 1–1.5 L/min, O2/H2S/CO/H2 0.5–1.0 L/min. H2S zero must use compressed air with 20.9%Vol O2 (never nitrogen) — flush 3 min, then span gas 2 min. Oxygen needs no zero. Typical life: catalytic ≈36 months (poison-sensitive), O2/toxic 24+ months, NDIR longest (immune to poisons). Accuracy degrades in oxygen-deficient atmospheres (O2 <6%v/v).
Technical Figures










Certifications & Compliance
Certificates shown as blurred previews only (no downloads). Request official copies and current validity from sales.