This page focuses on solution design for ammonia synthesis applications with actionable Honeywell product guidance.
| Level | Example setpoint | Interlock action |
|---|---|---|
| Low alarm AL1 | NH₃ 25 ppm / H₂ 10%LEL / H₂S 10 ppm | Local audible-visual + control room notice, start ventilation |
| High alarm AL2 | NH₃ 50 ppm / H₂ 20%LEL / H₂S 20 ppm | Area broadcast, feed valve closure, ESD pre-action |
| Fault | Sensor failure / 4–20 mA line break | Maintenance ticket; never leave muted > 24 h |
Wiring: use flame-retardant shielded cable for 4–20 mA loops; Modbus or fibre ring uplinks to the F&G system; redundant power for controllers in critical areas.