This page focuses on solution design for metallurgy applications with actionable Honeywell product guidance.
| Level | Example CO setpoint | Interlock action |
|---|---|---|
| Low alarm AL1 | 24–30 ppm (≈30 mg/m³) | Local audible-visual, start ventilation, alert personnel |
| High alarm AL2 | 50–100 ppm | Area broadcast, stop work, evacuate; shut off gas if required |
| O₂ alarm | <19.5% or >23% | No entry / immediate evacuation of confined spaces |
Interlock: CO high alarm at booster stations should trip compressors and open venting; holder-area alarms feed the plant-wide F&G network linked to dispatch.
Cast house and coke-oven alleys: extractive or shielded heads. CO at breathing height and holder piston tops. Wire to gas dispatch, not a beacon in the dust.