Honeywell XNX XNX-AMAV-MHCB1 – MPD catalytic 0–100 %LEL, mV, ATEX, Aluminium, M25

XNX-AMAV-MHCB1 is a factory-configured Honeywell XNX gas detector: mV personality, MPD catalytic bead 0–100 %LEL, ATEX / IECEx (INMETRO on selected MPD SKUs), 4 × M25, LM25 aluminium (painted), Modbus RTU + 4–20 mA HART, local HART port on the transmitter. Specify it for mixed hydrocarbon LEL points where infrared windows would fog or the stream is not methane/propane-specific.

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-MHCB1, 316SS XNX-AMSV-MHCB1, other approval XNX-UTAV-MHCB1. XNX-AMAV-MHCB1 · XNX-AMSV-MHCB1 · XNX-UTAV-MHCB1

XNX-AMAV-MHCB1 Honeywell XNX flammable gas (catalytic) Aluminium M25

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULA
M / TEntry M=M25; T=3/4" NPTM
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBM
N / HLocal HART port N=no; H=yesH
CB1MPD catalytic 0–100 %LELCB1

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-MHCB1, 316SS XNX-AMSV-MHCB1, other approval XNX-UTAV-MHCB1.

Technical specifications

CategoryTransmitter Configured
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeMPD catalytic 0–100 %LEL
TargetLEL / flammable gas (catalytic)
PrincipleMPD catalytic bead
OutputModbus RTU + 4–20 mA HART
Local HARTlocal HART port on the transmitter
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × M25
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsATEX / IECEx (INMETRO on selected MPD SKUs)
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

A poison-resistant MPD pellistor sees combustion heat across a wide hydrocarbon mix, including species an IR filter misses. It needs oxygen and hates silicones. Mount above light-gas releases and below heavy vapours; keep silicone sealants off the sinter.

Personality and replaceable parts

XNX-AMAV-MHCB1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD catalytic 0–100 %LEL. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Pump rooms, filling gantries and compressor packages still standardise on catalytic LEL because the gas slate is mixed. XNX holds 4–20 mA HART into the ESD matrix; magnetic non-intrusive calibration keeps the flameproof lid closed.

Selection contrast

P/NGasRangeOptionBody
XNX-AMSV-MHCB1LEL0–100 %LELModbus316SS
XNX-UTAV-MHCB1LEL0–100 %LELModbusAluminium
XNX-AMAV-MHIV1CH₄0–100 %LELModbusAluminium
XNX-AMAV-MHIF1C₃H₈0–100 %LELModbusAluminium
XNX-AMAV-MHIC1CO₂0–5 %v/vModbusAluminium
XNX-AMAV-MHNNNbody—ModbusAluminium
XNX-AMAV-NHCB1LEL0–100 %LELHARTAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-AMAV-MHCB1 (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × M25 entries—glands must match; do not retap XNX-AMAV-MHCB1. Land XNX-AMAV-MHCB1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-AMAV-MHCB1 lid stay non-intrusive. Keep silicones off the XNX-AMAV-MHCB1 pellistor; light hydrocarbons high, heavy vapours low.

FAQ

Alu/SS?
Choose by corrosion/weight; enclosure digit is in the P/N.
Calibration?
Per fitted sensor and target gas.
Which sensors?
CAT/IR/EC etc. via personality/sensor configuration digits.
Spares?
Use the family matrix for heads and accessories.
Enquiry?
Quote full P/N XNX-AMAV-MHCB1 plus sensor/enclosure/approval.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Availability: Not in stock — orders accepted; lead time approx. 16 weeks. Quote full P/N XNX-AMAV-MHCB1, gas/range and approval.