Honeywell XNX XNX-UTAV-FNIF1 – MPD IR propane 0–100 %LEL, mV, UL, Aluminium, 3/4" NPT

XNX-UTAV-FNIF1 is a factory-configured Honeywell XNX with MPD infrared propane 0–100 %LEL, mV personality, UL / cUL, 4 × 3/4" NPT, LM25 aluminium (painted), Foundation Fieldbus + 4–20 mA HART, no local HART port. Order it for LPG bullets and cylinder halls; methane IR (IV1) will under-read propane.

Same sensor, swap enclosure/approval: aluminium XNX-UTAV-FNIF1, 316SS XNX-UTSV-FNIF1, other approval XNX-AMAV-FNIF1. XNX-UTAV-FNIF1 · XNX-UTSV-FNIF1 · XNX-AMAV-FNIF1

XNX-UTAV-FNIF1 Honeywell XNX propane Aluminium 3/4" NPT

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULU
M / TEntry M=M25; T=3/4" NPTT
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBF
N / HLocal HART port N=no; H=yesN
IF1MPD IR propane 0–100 %LELIF1

Same sensor, swap enclosure/approval: aluminium XNX-UTAV-FNIF1, 316SS XNX-UTSV-FNIF1, other approval XNX-AMAV-FNIF1.

Technical specifications

CategoryTransmitter Configured
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeMPD IR propane 0–100 %LEL
TargetC₃H₈ / propane
PrincipleMPD infrared (propane)
OutputFoundation Fieldbus + 4–20 mA HART
Local HARTno local HART port
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × 3/4" NPT
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsUL / cUL
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

Propane is heavier than air and slides into pits. MPD IR tuned for C₃ does not need oxygen and ignores silicone poisons that kill CB1 beads. Mount 200–400 mm above grade at the pit lip, not on the roof.

Personality and replaceable parts

XNX-UTAV-FNIF1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD IR propane 0–100 %LEL. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

LPG tank farms, bottle-filling halls and kitchen-gas manifolds need a propane-specific IR trip. XNX hard-wires 4–20 mA HART to tank ESD; a handheld only proves the aisle you walked.

Selection contrast

P/NGasRangeOptionBody
XNX-UTSV-FNIF1C₃H₈0–100 %LELFFB316SS
XNX-AMAV-FNIF1C₃H₈0–100 %LELFFBAluminium
XNX-UTAV-FNCB1LEL0–100 %LELFFBAluminium
XNX-UTAV-FNIV1CH₄0–100 %LELFFBAluminium
XNX-UTAV-FNIC1CO₂0–5 %v/vFFBAluminium
XNX-UTAV-FNNNNbody—FFBAluminium
XNX-UTAV-NNIF1C₃H₈0–100 %LELHARTAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-UTAV-FNIF1 (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × 3/4" NPT entries—glands must match; do not retap XNX-UTAV-FNIF1. Land XNX-UTAV-FNIF1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-UTAV-FNIF1 lid stay non-intrusive. XNX-UTAV-FNIF1 propane belongs at the pit lip, not the roof.

FAQ

Does XNX-UTAV-FNIF1 work in oxygen-free LPG vapour space?
Yes. MPD IR on XNX-UTAV-FNIF1 does not combust the sample, so inerted LPG vapour spaces remain measurable.
Install?
Torque, entries and earthing per the manual.
Alu/SS?
Choose by corrosion/weight; enclosure digit is in the P/N.
Calibration?
Per fitted sensor and target gas.
Spares?
Use the family matrix for heads and accessories.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Availability: Not in stock — orders accepted; lead time approx. 16 weeks. Quote full P/N XNX-UTAV-FNIF1, gas/range and approval.

WhatsAppTop